All fire alarm systems must be fitted with a standby supply and this is achieved by using Sealed Lead Acid (SLA) batteries.
The standards state that in the event of a mains supply failure, the backup batteries should be able to run the system for a minimum of 24hrs, followed by 30minuites in full alarm condition (all sounders running). This applies to category M & L.

If the system is category P then the above applies if the building is continuously manned. If however the building is not continuously manned, then the standby time may need to be 72hrs.
Standby Battery Calculation

In order to calculate the standby battery size required, the following formula can be used;

Battery Size (Standby time in Amp Hours) = 1.25 x [(TALM x IALM) + (TSBY x (IQP + IQZ))]
Where;

TALM = Maximum time in hours required for the alarm [½ hour is most common time]
IALM = Total Alarm Current in amps for all alarm devices connected to the alarm circuits
TSBY = Standby time in hours for the system after mains failure [normally 24, 48 or 72 hr]
IQP = Quiescent current in amps of control panel in fault condition [because of mains failure]
IAP = Alarm current in amps of control panel
IQL = Quiescent current in amps of all loop devices, for instance an Ionisation Detector = 0.00005 Amp (50 μA) , Optical Detector = 0.0001 Amp (100 μA)

Typical Example
A system comprises of a 1 loop Premier Quatro panel, with 80 Fyreye Extra Addressable Optical Smoke Detectors, 15 Zeta Addressable Manual Call Points, 20 Zeta Addressable Securetone 2 Sounders and the required standby is 24 hours. It will need to operate in alarm for ½ hour.

Calculate the battery size required;
TALM = 0.5 Hr
IALM-SND = 20 x 0.004 =0.08A
TSBY = 24 Hr
IQP = 0.20A
IAP = 0.19A
IQL = 80 x 0.00044 + 15 x 0.001 + 20 x 0.0005 = 0.0602A
IALM = IALM-SND + IAP + IQL = 0.08 + 0.19 + 0.0602 = 0.3302

Therefore using the equation;
Battery Size (Standby time in Amp Hours) = 1.25 x [(TALM x IALM) + (TSBY x (IQP + IQL))]
Battery Size (Standby time in Amp Hours) = 1.25 x [(0.5 x 0.33) + (24 x (0.20 + 0.06))]
Battery Size (Standby time in Amp Hours) = 1.25 x [(0.5 x 0.33) + (24 x 0.26)]
Battery Size (Standby time in Amp Hours) = 1.25 x [0.165 + 6.24]
Battery Size (Standby time in Amp Hours) = 1.25 x 6.405
Battery Size (Standby time in Amp Hours) = 8.01 Amp Hours

For a system like this, 2 x 12V sealed lead acid batteries must be used each with a capacity greater than 8.01 Ah, for example, 12Ah.

About the Author

Felicity is a intermittent author, writing infrequent overviews in the UK about business security and fire safety matters. For addressable fire alarm systems as well as fire alarm systems, smoke alarm systems, carbon dioxide fire extinguisher and fire blankets then please visit our site for a complete range of fire safety products. Discount fire supplies - suppliers of fire suppression system online.

Article Directory Source: http://www.articlerich.com/profile/Felicity-Lightbody/39388




Click the XML Icon Above to Receive Articles Via RSS!

Page copy protected against web site content infringement by Copyscape

Do not copy content from the page unless you comply with our terms of service.
Plagiarism will be detected by Copyscape.